Basic Info.
Model NO.
LZCT723-10
Phase
Single
Operation Condition
Indoor
Usage
Measurement
Winding Form
Single Layer & Tightly Wound Type
Insulating Medium
Epoxy Resin
Installation
Busbar Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Class
0.2s, 0.2, 0.5s, 0.5
Ratio
30-600A/5A
Standards
IEC60044-1; IEC 61869-2; ANSI C57.13; Ntc 2205; GB
Weight
1.6kg
Working Temperature
-35°c to +55°c
Types
Bushing Type Current Transformer
Transport Package
Standard Export Carton
Specification
CE, ISO9001: 2008, IEC
Trademark
GFUVE
Origin
Beijing, China
HS Code
8504311000
Production Capacity
10000PCS/Month
Product Description
LZCT723-10 CHINA HIGH QUALITY HIGH VOLTAGE BUSHING TYPE CURRENT TRANSFORMER
LZCT series China high quality high voltage bushing type current transformer is suitable forcurrent measurement and microcomputer protection of electrical equipment in 10KV,35KV and 110KV AC power system.It is widely used in compact fully insulated ring network switchgears such as ABB-Safe Ring/Safe Plus...and cable distribution boxes.The transformer can be directly installed at the inlet andoutlet cables.The slice is imported silicon material. Thesemicircular ring core and secondary windings arevacuum poured by insulated resin.

P1, P2 is primary polarity terminal, S1, S2 is secondary polarity terminal.
P2, S2 is homonymous terminals (subtractive polarity).
PARAMETERS
Technical parameters | |
---|---|
Standards | IEC60044-1; IEC 61869-2; ANSI C57.13; NTC 2205; GB1208-2006 |
Rated primary current | 30-600A |
Rated load | ≤20VA |
Rated frequency | 50Hz or 60Hz |
Rated secondary current | 5A or 1A |
Rated short-time thermal current | 40kA, 1S |
Rated continuous thermal current | 120%I1n |
Secondary winding power-frequency voltage | 3kV, 1min |
Instrument security factor | FS≤10 |
Mechanical parameters | |
Dimensions (W×D×H) (mm) | φ82xφ130x50 |
Weight (kg) | 1.5 |
Operating conditions | |
Operating temperature | -35°C to +55°C |
Daily average temp | <+40°C |
Altitude | <3500 meters |
Condition | No existence of severely begrimed, erosive and radioactive gas in the air. Permission of long-term operation under rated current. |
TECHNICAL DATA
Type | LZCT723-10 | LZCT723-10 | ||||
---|---|---|---|---|---|---|
Purpose | Measuring current transformer | Protection current transformer | ||||
Ratio | Accuracy class and rated load(VA) | Accuracy class and rated load(VA) | ||||
I1/I2 | 0.2S | 0.2 | 0.5 | 10P15 | 10P10 | 10P5 |
30/1 | 1.5 | 0.5 | ||||
50/1 | 1.5 | 1.25 | ||||
75/1 | 2 | 1 | 2 | |||
100/1 | 2.5 | 1.5 | 2.5 | |||
200/1 | 3 | 1.25 | 2.5 | |||
300/1 | 2.5 | 3.5 | 1.25 | 2.5 | ||
400/1 | 2.5 | 3.5 | 5 | 1.25 | 2.5 | |
500/1 | 3.5 | 5 | 7.5 | 1.25 | 3 | |
600/1 | 5 | 7.5 | 10 | 1.5 | 3 | |
50/5 | 1 | |||||
75/5 | 1.5 | 1.5 | ||||
100/5 | 2.5 | 2.5 | ||||
150/5 | 3.75 | 2.5 | ||||
200/5 | 2.5 | 5 | 2.5 | 3.75 | ||
300/5 | 2.5 | 3.75 | 7.5 | 2.5 | 6.25 | |
400/5 | 5 | 7.5 | 10 | 3.75 | 7.5 | |
500/5 | 5 | 7.5 | 10 | 3.75 | 10 | |
600/5 | 7.5 | 12.5 | 15 | 3.75 | 10 |