Basic Info.
Model NO.
                                     DSE6120
                                 Output Type
                                     DC
                                 Cooling 
Method
                                     Method
Air Cooled
                                 Installation 
Method
                                     Method
Fixed
                                 Generator 
Type
                                     Type
Diesel Generator
                                 Color
                                     Blank
                                 Weight
                                     1kg
                                 Transport Package
                                     Carton Box
                                 Specification
                                     1kg
                                 Trademark
                                     yokden
                                 Origin
                                     Chongqing, China
                                 HS Code
                                     8537109090
                                 Production Capacity
                                     2000PCS/Month
                                 Product Description
 
   Generator Controller DSE6120 Replacement AMF controller Electronics
Full testing functions, can test all the electricity parameter and non electricity parameter of generator sets
Multi start successful conditions (RPM sensor, oil pressure, power)
Automatic start/stop, switch on and off (ATS), also have perfect symptom protection functions
         Control Funtion        
                 1. Auto-test Commercial power                                                                   
                 2. Emergence Stop         
                   3. Manual Start/STOP         
                   4. Long-Distance Start/Stop         
                   5. Auto quit of Start motor         
                   6. Double power swicth transfer controll         
                   Protection Funtion         
                   1. Low-Lubrition Oil         
                   2. Charging failure         
                   3. Over Voltage,Over load         
                   4. High water temperature         
                   5. Over frequency         
                   6. Low Frequency         
                   7. Start/Stop Failure          



 
         
                   Data Display                                             
                     1. Battery Voltage                                                                                                                                                                                                                                                                                  
             2. Oil pressure            
                         3. Operation Time            
                         4. Frequency            
                         5. Voltage            
                         6. Amper            
                         7. Water Temperature            
                         8. Speed                                                          
                         
           |                     Specification                    | |
|                     DC SUPPLY                    | |
|                    CONTINUOUS VOLTAGE RATING                   |                    8 V to 35 V Continuous                   | 
|                    CRANKING DROPOUTS                   |                    Able to survive 0 V for 50 mS                   | 
|                    MAXIMUM OPERATING CURRENT                   |                    100 mA at 12 V, 105 mA at 24 V                   | 
|                    MAXIMUM STANDBY CURRENT                   |                    60 mA at 12 V, 55 mA at 24 V                   | 
|                    MAXIMUM SLEEP CURRENT                   |                    40 mA at 12 V, 35 mA at 24 V                   | 
|                     OUTPUTS                    | |
|                    OUTPUT A (FUEL)                   |                    10 A short term, 5 A continuous,at supply voltage                   | 
|                    OUTPUT B (START)                   |                    10 A short term, 5 A continuous,at supply voltage                   | 
|                    AUXILIARY OUTPUTS C,D                   |                    2 A DC at supply voltage                   | 
|                     GENERATOR                    | |
|                    VOLTAGE RANGE                   |                    15 V to 415 V AC (Ph to N) 26 V to 719 V AC (Ph to Ph)                   | 
|                    FREQUENCY RANGE                   |                    3.5 Hz to 75 Hz                   | 
|                     DIMENSIONS                    | |
|                    OVERALL                   |                    126 mm x 158 mm x 43 mm                   | 
|                    PANEL CUT-OUT                   |                    184 mm x137 mm                   | 
|                    MAXIMUM PANEL THICKNESS                   |                    8 mm                   | 




 
          
      